Specification and information for Panasonic Standard condensing units to allow Twin Combinations
Note – twin only available on 10kW – 14kW Models
Please click here to select required indoor unit information from our Panasonic site.
Pipe sizes are as per Outdoor Unit tables on this page and indoor unit tables from relative pages here.
Features and Benefits
Power/Wiring
Panasonic PAC-i systems require a separate power supply to Indoor (3 Amp isolator for all units) and Outdoor Units. It is also possible to supply power to outdoor unit only, and run power to indoor via a 3 core flex from a field supplied fused terminal block or inline fuse. Please click here for instructions. A separate 2 core 0.75mm² screened cable will also be required for data connection
Three Phase Twin Split example
Piping
CZ-P224BK2BM Pipe Kit required for all PAC-i Standard Twin Split installations up to 14kW
CZ-P680BK2BM Pipe Kit required for all PAC-i Standard and Elite Twin Split installations from 20kW to 25kW
Multiples of the above required for Triple and Quad systems. Please confirm with Logicool
Advanced Technical Data
Note that 6kW model does not allow Twin connection
Outdoor Unit Technical Data | |||||
Combinations | Single | Single and Twin | |||
Model | U-60PZ2E5 | U-71PZ2E5 | U-100PZ2E5(8) | U-125PZ2E5(8) | U-140PZ2E5(8) |
Height (mm) | 695 | 695 | 996 | 996 | 1416 |
Width (mm) | 875 | 875 | 980 | 940 | 940 |
Depth (mm) | 320 | 320 | 370 | 340 | 340 |
Weight (kG) | 44 | 44 | 90 | 94 | 94 |
Airflow (m3/min) | 40 / 45 | 50 / 45 | 76 / 70 | 86 / 78 | 89 / 83 |
Sound Pressure Cooling (dBA) | 48 | 49 | 52 | 55 | 56 |
Sound Power Cooling (dBA) | 68 | 69 | 70 | 73 | 74 |
Liquid (mm(inches)) | 9.52 (3/8) | ||||
Gas (mm(inches)) | 15.88 (5/8) | ||||
Max Pipe Run (m) | 40 | 50 | |||
Max Pipe Lift (m) | 30 (15 if condenser is lower than IU) | ||||
Pre-charged to (m) | 30 | ||||
Standing Charge (kG) | 1.45 | 1.45 | 2.6 | 2.98 | 2.98 |
Additional Charge/m (g) | 35 | 35 | 45 | 45 | 45 |
Refrigerant | R32 | ||||
Phase | Single | Single (Three) | |||
Power Supply to | IU (5A) and OU or OU with feed to IU | ||||
Max Current (A) | 16.4 | 16.34 | 25.0 | 29.0 | 30.0 |
Fuse Rating (A) | 20 | 20 | 25 (16) | 32 (16) | 32 (16) |
Interconnecting | 2C Screen 0.75mm² |
||||
Twin Pipe Kit | CZ-P224BK2BM |
Three Phase Condensing Units – BIG PAC-i 20kw and 25kW Models
Outdoor Unit Technical Data | ||
Model | U-200PZH2E8 | U-250PZH2E8 |
Combinations | Twin/Triple/Quad | |
Height (mm) | 1500 | 1500 |
Width (mm) | 980 | 980 |
Depth (mm) | 370 | 370 |
Weight (kG) | 117 | 128 |
Airflow (l/sec) Cool/Heat | 2733 / 2733 | 2667 / 2667 |
Sound Pressure Cooling (dBA) | 59 | 59 |
Sound Pressure Heating (dBA) | 61 | 63 |
Liquid (mm(inches)) | 1 1/8 | 1 1/8 |
Gas (mm(inches)) | 3/8 | 1/2 |
Max Pipe Run (m) | 90 | 90 |
Max Pipe Lift (m) | 30 | 30 |
Pre-charged to (m) | 30 | 30 |
Standing Charge (kG) | 4.2 | 5.8 |
Additional Charge per meter (g) | 60 | 80 |
Refrigerant | R32 | |
Phase | Three | |
Power Supply to | IU (5A) and OU or OU with feed to IU | |
Running Current (Cool - Heat) | TBC | TBC |
Input Power (Cool - Heat) | 6.06 / 6.21 | 7.46 / 8.21 |
Fuse Rating (A) | 32 | 32 |
Interconnecting | 2C Screen 0.75mm? | |
Twin Pipe Kit | CZ-P680BK2BM | |
Triple Pipe Kit | CZ-P3HPC2BM | No Combination |
Quad Pipe Combination | CZ-P680BK2BM x 1 and CZ-P224BK2BM x 2 |