MSY-TP C/Only R32 Wall – Comms Rooms

Enquire Now

MSZ-TP  High Efficiency R32 Wall Mounted System

The M Series MSY-TP R32 High SHF wall mounted system blends energy efficiency with a modern white design. This cooling only unit has a high sensible cooling capacity, making it ideal for small computer rooms or areas that require a greater degree of sensible cooling. The MSY-TP also utilises low GWP R32 refrigerant.

NOTE: POWER SUPPLY TO INDOOR UNIT

The MSY-TP range comes in 3.5 and 5.0kW capacity sizes and is new to the UK market. It is designed for Cooling Only Comms/IT room applications

Note that the MSY-TP requires an additional MAC-334IF-E interface and PAR-33MAA / PAR-40MAA wired remote controller.

Model Reference
UK. Cool
(kW)

Nom. Cool
(kW)

Max
Pipe
(m)
EuP Lot 10
Energy Rating

Fuse
Rating
(Amps)

Pipe
Size
Gas

Pipe
Size
Liquid

Electrical
Supply
Indoor UnitOutdoor UnitSEER
MSY-TP35VFMUZ-TP35VF3.473.50209.00103/81/4Single (Indoor)
MSY-TP50VFMUZ-TP50VF4.965.00208.00103/81/4Single (Indoor)

 

Feature and Benefits

  • Compact and stylish white design
  • High sensible cooling ability
  • Highly energy efficient, utilising low GWP R32 refrigerant
  • Built in CN105 allowing for connection of the MAC-567IF Wi-Fi interface, enabling control and monitoring using a smart phone, tablet or PC via the MELCoud app
  • Weekly timer provides greater control of scheduling
  • Optional Infra Red Controller – Part Number E22X33426

 

Advanced Technical Data

The SHF figures are based on nominal conditions. Note power to indoor and the system requires an additional MAC-334IF-E interface and PAR-40MAA wired remote controller

Indoor Units

Indoor Unit Technical DataModel Reference
MSY-TP35VFMSY-TP50VF
Cooling (kW) - UK3.47 (1.48 - 3.96)4.96 (1.48 - 5.65)
Cooling (kW) - Nominal3.50 (1.50 - 4.00)5.00 (1.50 - 5.70)
SHF (nominal & UK)0.980.82
Sound Pressure - Cooling (dBA)31-36-40-4531-36-40-45
Height (mm)305305
Width (mm)923923
Depth (mm)250250
Weight (kG)1010
Air Flow - (l/sec) Cooling82-98-118-145-190168-193-228-273168-193-228-273

(Power to Indoor Unit – adapter and controller required)

Outdoor Units

Outdoor Unit Technical DataModel Reference
MUY-TP35VFMUY-TP50VF
Height (mm)550
Width (mm)800
Depth (mm)285
Weight (kG)3434
Sound Pressure - Cool (dBA)4547
Liquid (mm(inches))6.35 (1/4)
Gas (mm(inches))9.52 (3/8)
Max Pipe Run20
Max Pipe Lift12
Pre-charged to (m)7
Standing Charge (kG)0.85
Additional grams per metre10
RefrigerantR32
PhaseSingle
Power Supply toIndoor
Max Running Current (A)8.4613.6
Fuse Rating (A)10
Interconnecting3C + E
System Power Input (Cool - UK) - kW0.641.12
Back to products
Add selected to wishlist