Mitsubishi Electric’s new Multi Density systems combine the efficiency, quality and simplicity of VRF with high performance close coupled air conditioning units.
The range is particularly suitable for high density racks and blade server cooling in data centres. It is able to cope with the high density of the thermal load, putting the air conditioning unit directly within the rows of racks to cool the localised heat sources (hot spots).
Multi Density is ideal for applications where high sensible cooling and close control of temperature
in high density applications is required. This system consists of multiple indoor ‘coolside’ close coupled
air conditioners connected to a City Multi VRF outdoor unit. The result is a full inverter multi-split
system, designed according to the best quality standards and dedicated to the most reliable I.T. environments.
Key Features
Technical Data
CRAC UNITS (Computer Room Air Conditioning) | m-MRAC G02 009 m-MROW G02 009 | m-MRAC G02 015 m-MROW G02 015 | m-MRAC G02 025 m-MROW G02 025 | ||
COOLING CAPACITY | Total kW*1 | 10.6 | 16.6 | 28.6 | |
Sensible | 9.6 | 15.7 | 27.4 | ||
SHR*2 | 0.91 | 0.94 | 0.96 | ||
EC SUPPLY FAN (no.) | 2 | 4 | 5 | ||
AIRFLOW (m³/h) | 1500 | 2700 | 4200 | ||
NOMINAL EXTERNAL STATIC PRESSURE (Pa) | 20 | 20 | 20 | ||
MAX EXTERNAL STATIC PRESSURE (Pa) | 60 | 60 | 60 | ||
POWER INPUT (kW)*3 | 0.18 | 0.34 | 0.85 | ||
REFRIGERANT | R410A | R410A | R410A | ||
REFRIGERANT CIRCUITS (n°) | 1 | 1 | 1 | ||
AIR FILTERS | NO. | 2 | 2 | 2 | |
Extended filtering surface (m²) | 0.35 | 0.35 | 0.35 | ||
Efficiency [ISO EN 16890] (COARSE) | 0.4 | 0.4 | 0.4 | ||
SOUND LEVEL [ISO 3744] (dB(A))*4 | Pressure Level | 63.5 | 64.5 | 70.5 | |
Power Level | 79 | 80 | 86 | ||
POWER | Volts/Ph/Hz | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | |
ABSORBED CURRENT | (A)*3 | 0.8 | 1.5 | 4 | |
STARTING CURRENT | (A) | 2.9 | 5.8 | 7.3 | |
DIMENSIONS | Width (mm) | 300 | 300 | 300 | |
Depth (MROW / MRAC) (mm) | 1000 / 1200 | 1000 / 1200 | 1000 / 1200 | ||
Height (mm) | 2085 | 2085 | 2085 | ||
NET WEIGHT (kg) | In-Row | 175 | 190 | 193 | |
Enclosure | 185 | 200 | 203 | ||
CONNECTIONS - Pipes diameter | Gas (Ø Inch) | 3/4" | 7/8" | 1" | |
Liquid (Ø Inch) | 1/2" | 5/8" | 3/4" | ||
Condensate (Ømm)*5 | 16 | 16 | 16 | ||
Power supply wiring cable | (no. x mm²)*6 | 3G1.5 | 3G1.5 | 3G1.5 |
OUTDOOR UNITS | m-MOCU G02 050 | 2 x m-MOCU G02 050 | |
RATED COOLING CAPACITY | kW | 50 | 50 x 2 |
SYSTEM EER*2 | kW/kW | 2.96 | 3.24 |
SOUND PRESSURE LEVEL (dB(A)) | Cooling | 65 | 68 |
WEIGHT | (kG) | 304 | 304 x 2 |
DIMENSIONS (mm) | Width (mm) | 1650 | 1650 |
Depth (mm) | 740 | 740 | |
Height (mm) | 1750 | 1750 (x2) | |
POWER SUPPLY | (V / Hz) | 380-415v, 50Hz | 380-415v, 50Hz |
PHASE | 3 | 3 | |
OUTDOOR POWER INPUT (kW) | kW - Cooling (nom.) | 15.2 | 13.7 |
STARTING CURRENT | (A) | 27.8 | 27.8 x 2 |
MAX RUNNING CURRENT (COOL) | (A) | 37.6 | 37.6 x 2 |
FUSE RATING (BS88) - HRC (A) | (A) | 40 | 40 x 2 |
MAINS CABLE | No. Cores | 5G6 | 5G6 |
MAX PIPE LENGTH (m) | (m) | 165 | 165 |
MAX HEIGHT DIFFERENCE (m) | (m) | 50 (40*7) | 50 (40*7) |
CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) | R410A (GWP 2088) | 11.8 / 24.6 | 11.8 / 24.6 x 2 |
GUARANTEED OPERATING RANGE (°C) | Max Temp | 45 | 45 |
Min Temp | -15 | -15 |
Notes: THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD. *1 All data are refers to the Rating Configuration with 2x m-MROW-Z G02 F/S 025 @35°C Outdoor Temperature and 35°C/27%rh
Indoor Temperature. *2 SHR = Sensible cooling capacity / Total cooling capacity. *3 Corresponding to the nominal ESP=20Pa. *4 Sound pressure level on air return at 1m. *5 Rubber pipe – refers to internal diameter. *6 Minimum section.
It’s possible to connect indoor units with a sum of sizing from 25 to 75. These units contain <HFC R410A [GWP100 2088]> fluorinated greenhouse gas. *7 When outdoor unit is below indoor unit.