The Mitsubishi Electric AIRME Compact Air Handling Units (AHU’s) utilise a frameless structure to achieve a line-up of units that are as compact as possible, maximising air tightness and improving thermal properties.
The Mitsubishi Electric s-AIRME HR-P range of AHU’s utilises a combination of Mr Slim R32 Power Inverter heat pump technology, energy efficient plate heat exchanger heat recovery technology, and an integrated control system. This integration of technologies results in highly advanced, efficient systems that are easy to install and commission, making them ideal for offices, shopping centres, theatres and other large, open spaces.
s-AIRME-G07 HR-P C
Unit Technical Data | ||||||
Model | s-AIRME-G07 HR-P C 3000 | s-AIRME-G07 HR-P C 5000 | s-AIRME-G07 HR-P C 7500 | s-AIRME-G07 HR-P C 10000 | s-AIRME-G07 HR-P C 12500 | s-AIRME-G07 HR-P C 15000 |
AIR VOLUME DATA | ||||||
Max Air Volume m³/hr | 3000 | 5000 | 7500 | 10000 | 12500 | 15000 |
Rated Airflow Range m³/s | 0.56 - 0.83 | 0.91 - 1.38 | 1.19 - 2.08 | 1.73 - 2.77 | 2.19 - 3.47 | 2.35 - 4.16 |
External Static Pressure (Standard Fans) | 500 | 300 | 500 | 300 Supply / 500 Return | 300 | 500 |
External Static Pressure (OPTIONAL High Static Fans) | - | 500 | - | 500 | 500 | - |
COOLING CAPACITY | ||||||
DX Coil Capacity kW | 19.50 | 31.50 | 43.50 | 63.40 | 77.90 | 87.50 |
Heat Recovery Capacity kW | 8.89 | 14.80 | 22.70 | 30.00 | 37.30 | 44.50 |
Total Capacity kW | 28.39 | 46.30 | 66.20 | 93.40 | 115.20 | 132.00 |
HEATING CAPACITY | ||||||
DX Coil Capacity kW | 16.70 | 27.20 | 36.60 | 53.50 | 66.80 | 73.20 |
Wheel Recovery Capacity kW | 20.60 | 34.30 | 53.10 | 70.10 | 87.20 | 110.00 |
Total Capacity kW | 37.30 | 61.50 | 89.70 | 123.60 | 154.00 | 183.20 |
HEAT RECOVERY EFFICIENCY | ||||||
Heat Recovery Efficiency (Cool) % | 73.80 | 73.50 | 75.30 | 74.60 | 74.30 | 73.90 |
Heat Recovery Efficiency (Heat) % | 72.70 | 72.70 | 74.60 | 74.00 | 73.60 | 73.90 |
OPERATING RANGES | ||||||
On Coil Cooling (°CDB) | 15 - 32 | |||||
On Coil Heating (°CDB) | 5 - 28 | |||||
Supply Air Cooling (°CDB) | 12 - 30 | |||||
Supply Air Heating (°CDB) | 17 - 28 | |||||
Auto Cooling/Heating (°CDB) | 19 - 28 | |||||
POWER CONSUMPTION DATA (AR FUNCTION version C Model R32 - CHECK SYSTEM TYPE FOR FULL DATA) | ||||||
Delivery fan(s) (300Pa) | 0.66 / 2.50 | 1.68 / 2.50 | 1.45 / 4.20 | 1.89 / 4.20 | 2.43 / 4.20 | 3.17 / 4.20 |
Transformers | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 |
Total of sAIRME (Nom/Max) | 1.14 / 3.00 | 2.17 / 3.00 | 1.90 / 4.70 | 2.29 / 4.70 | 2.83 / 4.70 | 3.64 / 4.70 |
SPECIFIC FAN POWER (SFP int @ 400Pa ) - W/(l/s) | 0.775 | 0.936 | 0.812 | 0.736 | 0.810 | 0.691 |
SOUND POWER (dBA) LEVEL INFORMATION | ||||||
Fresh/Outdoor | 82 | 89 | 85 | 85 | 86 | 88 |
Supply | 82 | 89 | 85 | 85 | 86 | 88 |
Return | 80 | 88 | 84 | 85 | 86 | 87 |
Exhaust | 80 | 88 | 84 | 85 | 86 | 87 |
Breakout | 64 | 74 | 67 | 67 | 71 | 70 |
DIMENSIONAL INFORMATION | ||||||
Width (mm) | 2950 | 2950 | 3200 | 3650 | 3775 | 3946 |
Depth (mm) | 1385 | 1785 | 1885 | 2185 | 2385 | 2585 |
Height (mm) | 1675 | 1675 | 2200 | 2280 | 2480 | 2480 |
Weight (kG) | 750 | 950 | 1250 | 1600 | 1750 | 2100 |
FILTRATION AND CONSTRUCTION | ||||||
Fresh Air First Stage | ISO Coarse 50% / G4 | |||||
Fresh Air Second Stage | ISO ePM1 50% / F7 Bag Filter | |||||
Return Air Filtration | ISO Coarse 50% / G4 | |||||
Construction | 60mm Sandwich Panels with Thermal Break, Insulation: 45kG/m3 density Polyurethane Foam | |||||
EN1886 ACHIEVED CLASSES | (Deflection/Leakage/Filter/Thermal Bridging) Class - D1(M), L3, T2, TB4 | |||||
COMPATIBLE MR. SLIM OUTDOOR UNITS | ||||||
Power Inverter Model | 1 x PUZ-ZM200 | 1 x PUZ-ZM125 | 1 x PUZ-ZM200 | 2 x PUZ-ZM200 | 4 x PUZ-ZM200 | 2 x PUZ-ZM200 |
1 x PUZ-ZM200 | 1 x PUZ-ZM250 | 1 x PUZ-ZM250 | 2 x PUZ-ZM250 | |||
Refrigerant | R32 | |||||
Pipe Run (m) | 30 |