Hitachi’s Light Commercial range of Air Conditioning equipment bridges the gap between domestic and commercial product, offering high efficiencies, quality engineering and stylish design. These products are targeted at the Light Commercial market such as small to medium sized commercial office developments, restaurants and retail applications.
The compact 600 x 600 cassette fits perfectly into a standard ceiling module allowing for a quick and easy installation.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) | Pipe Gas | Pipe Liquid | R22 replace? | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | ||||||||
RAI-25RPE | RAC-25NPE | 2.50 | 3.50 | 20 | 4.30 | 6.20 | 16 | 3/8 | 1/4 | Yes | Single |
RAI-35RPE | RAC-35NPE | 3.50 | 4.80 | 20 | 4.30 | 6.50 | 16 | 3/8 | 1/4 | Yes | Single |
RAI-50RPE | RAC-50NPE | 5.00 | 6.00 | 30 | 4.40 | 6.20 | 20 | 1/2 | 1/4 | Yes | Single |
RAI-60RPE | RAC-60NPE | 6.00 | 7.00 | 30 | 4.40 | 6.20 | 20 | 1/2 | 1/4 | Yes | Single |
System includes Indoor Unit, PAP-56NAMS Grille, Outdoor Unit and SPX-RCKA3 Infra-Red, Wireless controller. Other controller options are available.
Features and Benefits
Wiring
Power supply to Outdoor Unit with 3C + E interconnecting cable.
Product Images
Advanced Technical Data
Indoor Unit Technical Data | Model Reference | |||
RAI-25RPE | RAI-30RPE | RAI-50RPE | RAI-60RPE | |
Cooling (kW) - Nominal | 2.50 (0.90 - 3.00) | 3.50 (0.90 - 4.00) | 5.00 (1.20 - 5.80) | 6.00 (1.20 - 6.50) |
Heating (kW) - Nominal | 3.50 (0.90 - 5.00) | 4.80 (0.9 - 6.60) | 6.00 (1.20 - 6.80) | 7.00 (1.20 - 8.00) |
Heating capacity at -7C | 4.20 | 4.80 | ||
System SCOP | 4.30 | 4.40 | ||
System SEER | 6.20 | 6.50 | 6.20 | |
Sound Pressure - Cooling (dBA) | 38/35/31/27 | 40/37/33/27 | 43/39/35/29 | |
Height (mm) | 285 (30) | |||
Width (mm) - (Grille) | 570 (620) | |||
Depth (mm) - (Grille) | 570 (620) | |||
Weight (kG) - (Grille) | 17 (2.8) | |||
Air Flow - Cooling (m³/hr) | 660/590/505/360 | 720/630/540/390 |
Outdoor Unit Technical Data | Model Reference | |||
RAC-25NPD | RAC-35NPD | RAC-50NPD | RAC-60NPD | |
Height (mm) | 548 | 548 | 750 | 750 |
Width (mm) | 750 | 750 | 850 | 850 |
Depth (mm) | 288 | 288 | 298 | 298 |
Weight (kG) | 32.5 | 32.5 | 50 | 50 |
Sound Pressure - Cooling (dBA) | 48 | 50 | ||
Liquid (mm(inches)) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) |
Gas (mm(inches)) | 9.52 (3/8) | 9.52 (3/8) | 12.7 (1/2) | 12.7 (1/2) |
Max Pipe Run | 20 | 20 | 30 | 30 |
Max Pipe Lift | 10 | 10 | 20 | 20 |
Pre-charged to (m) | 20 | 20 | 30 | 30 |
Standing Charge (kG) | 1.50 | 1.50 | ||
Additional Charge per metre | N/A - Pre-charged to 20m | N/A - Pre-charged to 30m | ||
Refrigerant | R32 | |||
Phase | Single | |||
Power Supply to | Outdoor | |||
Start Current (A) | 10.00 | |||
Fuse Rating (A) | 20 | |||
Interconnecting | 3C + E* | |||
System Power Input (Cool/Heat) - kW | 1.420 / 1.570 | 1.710 / 1.840 | ||
Working range (cooling / heating) | -15°C - 46°C // -15°C - 24°C |