NEW FLOOR CONSOLE R32 GAS
New Floor Console with new nanoe™ X air-purifying system:
outstanding efficiency A++, comfort (Super Quiet technology only 20dB(A)) and healthy air combined with a breakthrough design
Please click here for the Panasonic Nanoe-X Concentration Simulator.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) | Pipe Size Gas | Pipe Size Liquid | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | |||||||
CS-Z25UFEAW | CU-Z25UBEA | 2.50 | 3.40 | 20 | 4.60 | 7.90 | 16 | 3/8 | 1/4 | Single |
CS-Z35UFEAW | CU-Z35UBEA | 3.50 | 4.30 | 20 | 4.60 | 8.10 | 16 | 3/8 | 1/4 | Single |
CS-Z50UFEAW | CU-Z50UBEA | 5.00 | 5.80 | 30 | 4.30 | 6.70 | 16 | 1/2 | 1/4 | Single |
System includes Infra Red Controller
(Optional Hardwired Controller CZ-RD514C and Wi-Fi Interface TACG1 also available)
Product Description
Upper & lower vane blow Console designed for discreet integration on walls, and for high performance, specifically in heat mode even when the outside temperature is as low as -15°C. Double airflow for improved comfort and temperature dispersion: through the top for an effi cient cooling mode, through the bottom for quick heating. Upper & lower vane blow Optimum air fl ow from the top and bottom of the unit assures that even your feet are kept comfortably warm. (Only during heating)
Features and Benefits
Product Images
Power and Wiring Information
All wiring on Panasonic RAC products is 3C+E Interconnecting. Power supply to Outdoor Unit unless specified.
Note that Power Supply can be fed to either Indoor or Outdoor unit.
Advanced Technical Data
Indoor Unit Technical Data | Model Number | ||
CS-Z25UFEAW | CS-Z35UFEAW | CS-Z50UFEAW | |
Cooling (kW) - Nominal | 2.50 (0.85 - 3.40) | 3.50 (0.85 - 3.80) | 4.20 (0.90 - 5.70) |
Heating (kW) - Nominal | 3.40 (0.85 - 5.00) | 4.30 (0.85 - 6.00) | 5.80 (0.90 - 8.10) |
Cooling (kW) - Max UK Condition | 3.00 | 4.00 | 5.00 |
Heating (kW) - Max UK Condition | 5.40 | 6.60 | 7.25 |
Sensible Cooling Duty (UK) | 1.90 | 2.66 | 3.19 |
Sound Pressure - Cooling (dBA) | 38 / 25 / 20 | 39 / 26 / 20 | 44 / 31 / 27 |
Sound Pressure - Heating (dBA) | 38 / 25 / 19 | 39 / 26 / 19 | 46 / 33 / 29 |
Height (mm) | 600 | ||
Width (mm) | 750 | ||
Depth (mm) | 207 | ||
Weight (kG) | 13 | ||
Air Flow - Cooling (m³/min) | 9.60 | 9.90 | 11.60 |
Air Flow - Heating (m³/min) | 9.90 | 10.10 | 13.20 |
Outdoor Unit Technical Data | Model | |||
CU-Z25UBEA | CU-Z35UBEA | CU-Z50UBEA | CU-Z60UBEA | |
Height (mm) | 542 | 619 | 695 | 695 |
Width (mm) | 780 | 824 | 875 | 875 |
Depth (mm) | 289 | 299 | 320 | 320 |
Weight (kG) | 33 | 35 | 43 | 43 |
Airflow Cooling (m3/min) | 28.7 | 34.3 | 39.7 | 42.6 |
Sound Pressure Cooling (dBA) | 46 | 48 | 48 | 49 |
Sound Pressure - Heating (dBA) | 47 | 48 | 48 | 50 |
Liquid (mm(inches)) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) |
Gas (mm(inches)) | 9.52 (3/8) | 9.52 (3/8) | 12.7 (1/2) | 12.7 (1/2) |
Max Pipe Run (m) | 20 | 20 | 30 | 30 |
Max Pipe Lift (m) | 15 | 15 | 20 | 20 |
Pre-charged to (m) | 7.5 | 7.5 | 7.5 | 7.5 |
Standing Charge (kG) | 0.88 | 0.93 | 1.13 | 1.13 |
Refrigerant | R32 | |||
Additional Charge g/m | 10 | 10 | 15 | 15 |
Phase | Single | |||
Power Supply to | Outdoor | |||
Fuse Rating (A) | 16 | TBC | ||
Interconnecting | 3C + E | |||
System Power Input (Cool/Heat) - watts | 0.52/0.76 | 0.86/1.08 | 1.39/1.55 | 2.04/2.16 |