The 8-10HP from Panasonic is ideally suited for large retail applications and other large areas not needing the higher capacities of VRF systems.
Indoor unit can be disassembled down to Heat Exchanger and Fan Assemblies to allow for installation in tight spaces. Ideal for Retrofit solutions.
The lightweight and compact design enables easier installation in any commercial space.
The twin fan system saves valuable footprint compared to traditional 8-10HP systems which are larger and therefore require more space.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) In/Out | Pipe Size Gas | Pipe Size Liquid | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | |||||||
S-200PE3E5B | U-200PZH2E8 | 19.5 | 22.4 | 90 | 3.61 | 5.25 | 5 / 32 | 1 1/8 | 3/8 | Three |
S-250PE3E5B | U-250PZH2E8 | 23.2 | 28 | 90 | 3.61 | 4.84 | 5 / 32 | 1 1/8 | 1/2 | Three |
Features and Benefits
Power/Wiring
Panasonic PAC-i systems require a separate power supply to Indoor (3 Amp isolator for all units) and Outdoor Units. It is also possible to supply power to outdoor unit only, and run power to indoor via a 3 core flex from a field supplied fused terminal block. A separate 2 core 0.75mm² screened cable will also be required for data connection
Product Images
Advanced Technical Data
Indoor Units
Indoor Unit Technical Data | ||
Model | S-200PE3E5B | S-250PE3E5B |
Cooling (kW) - Nominal | 19.5 | 23.2 |
Heating (kW) - Nominal | 22.4 | 28 |
Cooling (kW) - Max SEER Condition | 21 | 27 |
Heating (kW) - Max SCOP Avg Climate Condition | 25 | 29 |
Sensible Heat Ratio (SHR) | TBC | TBC |
41/44/46 | 41/44/46 | 42/45/47 |
Statuc Pressure (Pa) | 75/120/180 | 75/130/180 |
Height - mm | 486 | 486 |
Width - mm | 1456 | 1456 |
Depth - mm | 916 | 916 |
Weight - kG (grille) | 86 | 88 |
Air Flow Rate (l/sec) | 883/1050/1200 | 983/1200/1400 |
Fused Spur (A) | 5 | 5 |
Condensing Units
Outdoor Unit Technical Data | ||
Model | U-200PZH2E8 | U-250PZH2E8 |
Combinations | Twin/Triple/Quad | |
Height (mm) | 1500 | 1500 |
Width (mm) | 980 | 980 |
Depth (mm) | 370 | 370 |
Weight (kG) | 117 | 128 |
Airflow (l/sec) Cool/Heat | 2733 / 2733 | 2667 / 2667 |
Sound Pressure Cooling (dBA) | 59 | 59 |
Sound Pressure Heating (dBA) | 61 | 63 |
Liquid (mm(inches)) | 1 1/8 | 1 1/8 |
Gas (mm(inches)) | 3/8 | 1/2 |
Max Pipe Run (m) | 90 | 90 |
Max Pipe Lift (m) | 30 | 30 |
Pre-charged to (m) | 30 | 30 |
Standing Charge (kG) | 4.2 | 5.8 |
Additional Charge per meter (g) | 60 | 80 |
Refrigerant | R32 | |
Phase | Three | |
Power Supply to | IU (5A) and OU or OU with feed to IU | |
Running Current (Cool - Heat) | TBC | TBC |
Input Power (Cool - Heat) | 6.06 / 6.21 | 7.46 / 8.21 |
Fuse Rating (A) | 32 | 32 |
Interconnecting | 2C Screen 0.75mm? | |
Twin Pipe Kit | CZ-P680BK2BM | |
Triple Pipe Kit | CZ-P3HPC2BM | No Combination |
Quad Pipe Combination | CZ-P680BK2BM x 1 and CZ-P224BK2BM x 2 |