Hitachi’s Light Commercial range of Air Conditioning equipment bridges the gap between domestic and commercial product, offering high efficiencies, quality engineering and stylish design. These products are targeted at the Light Commercial market such as small to medium sized commercial office developments, restaurants and retail applications.
This compact concealed ducted solution is low height (270mm) with high performance (150Pa ESP). It allows flexibility and individual zone control of each interior space to maintain consistent temperatures and airflow distribution.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) | Pipe Gas | Pipe Liquid | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | |||||||
RAD-25RPE | RAC-25NPE | 2.50 | 3.50 | 20 | 4.30 | 6.20 | 16 | 3/8 | 1/4 | Single |
RAD-35RPE | RAC-35NPE | 3.50 | 4.80 | 20 | 4.30 | 6.50 | 16 | 3/8 | 1/4 | Single |
RAD-50RPE | RAC-50NPE | 5.00 | 6.00 | 30 | 4.00 | 6.20 | 20 | 1/2 | 1/4 | Single |
RAD-60RPE | RAC-60NPE | 6.00 | 7.00 | 30 | 4.00 | 6.20 | 20 | 1/2 | 1/4 | Single |
RAD-70PPD | RAC-70NPD | 7.00 | 8.00 | 30 | 4.00 | 6.10 | 20 | 1/2 | 1/4 | Single |
System includes Indoor Unit, Outdoor Unit and SPX-WKT3A controller. Other controller options are available.
Features and Benefits
Wiring
Power supply to Outdoor Unit with 3C + E interconnecting cable.
Product Images
Advanced Technical Data
Indoor Unit Technical Data | Model Reference | ||||
RAD-25PPD | RAD-35PPD | RAD-50PPD | RAD-60PPD | RAD-70PPD | |
Cooling (kW) - Nominal | 2.50 (0.90 - 3.00) | 3.50 (0.90 - 4.00) | 5.00 (1.20 - 5.80) | 6.00 (1.20 - 6.50) | 7.00 (1.50 - 8.00) |
Heating (kW) - Nominal | 3.50 (0.90 - 5.50) | 4.80 (0.90 - 6.60) | 6.00 (1.20 - 6.80) | 7.00 (1.20 - 8.00) | 8.00 (1.50 - 8.50) |
System SCOP | 4.30 | 4.30 | 4.00 | 4.00 | |
System SEER | 6.20 | 6.50 | 6.20 | 6.10 | |
Sound Pressure - Cooling - (dBA) | 41/37/33/30 | 41/37/33/30 | 39/35/32/29 | ||
Sound Power - Cooling (dBA) | 57 | 57 | 53 | ||
Height (mm) | 235 | 235 | 270 | ||
Width (mm) - (Grille) | 750 | 750 | 900 | ||
Depth (mm) - (Grille) | 400 | 400 | 720 | ||
Weight (kG) - (Grille) | 16 | 16 | 32 | ||
Air Flow - Cooling (m³/hr) | 510/450/390/330 | 510/450/390/330 | 1140/800/540/350 |
Outdoor Unit Technical Data | Model Reference | ||||
RAC-25NPE | RAC-35NPE | RAC-50NPE | RAC-60NPE | RAC-70NPE | |
Height (mm) | 548 | 548 | 750 | 750 | 800 |
Width (mm) | 750 | 750 | 850 | 850 | 850 |
Depth (mm) | 288 | 288 | 298 | 298 | 298 |
Weight (kG) | 32.5 | 32.5 | 50 | 50 | 52 |
Sound Pressure - Cooling (dBA) | 48 | 48 | 50 | 50 | 52 |
Liquid (mm(inches)) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) |
Gas (mm(inches)) | 9.52 (3/8) | 9.52 (3/8) | 12.7 (1/2) | 12.7 (1/2) | 15.88 (5/8) |
Max Pipe Run | 20 | 20 | 30 | 30 | 30 |
Max Pipe Lift | 10 | 10 | 20 | 20 | 20 |
Pre-charged to (m) | 20 | 20 | 30 | 30 | 30 |
Standing Charge (kG) | 0.9 | 0.9 | 1.50 | 1.50 | 1.60 |
Additional Charge per metre | N/A - Pre-charged to 20m | N/A - Pre-charged to 30m | |||
Refrigerant | R32 | ||||
Phase | Single | ||||
Power Supply to | Outdoor | ||||
Start Current (A) | 10.00 | ||||
Fuse Rating (A) | 20 | ||||
Interconnecting | 3C + E* | ||||
System Power Input (Cool/Heat) - kW | 0.600/0.880 | 0.950/1.260 | 1.420 / 1.570 | 1.710 / 1.840 | 2.110 / 2.200 |
Working range (cooling / heating) | -10°C - 46°C // -15°C - 24°C | -15°C - 46°C // -15°C - 24°C |