High precision air conditioners are ideal for applications where high sensible cooling and close control of temperature and humidity are required.
The i-NEXT direct expansion air cooled range incorporates full inverter driven BLDC Mitsubishi Electric
compressors, perfect for keeping room conditions constant under varying loads, whilst being highly efficient.
Key Features
Technical Data
CRAC Model Reference (i-NEXT DX...) | 012 M1 S E1 | 018 M1 S E2 | 022 M1 S E3 | 030 M1 S E4 | 047 M1 S E5 | 042 M2 D E5 | 068 M2 D E7 | 094 M2 D E8 | 120 M4 D E9 *1 | 150 M4 D E9 *1 | |
Capacity (kW)*2 | Range | 3.1 - 10.4 | 7.0 - 21.9 | 7.7 - 24.0 | 12.2 - 39.4 | 17.4 - 54.1 | 15.0 - 49.3 | 24.0 - 79.1 | 33.3 - 105.0 | 25.8 - 119.0 | 34.9 - 139.5 |
Capacity (kW)*2 | Nominal | 9.1 | 17.8 | 22.2 | 30.7 | 48.2 | 43.8 | 68.6 | 93.9 | 100 | 129 |
SHF | Nominal | 1 | 0.99 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
EER*3 | Nominal | 4.3 | 3.7 | 3.69 | 3.97 | 3.74 | 3.74 | 3.88 | 3.74 | 3.53 | 3.33 |
Power Input (kW) | Nominal | 2.12 | 4.81 | 6.01 | 7.73 | 12.9 | 11.7 | 17.7 | 25.1 | 28.3 | 38.7 |
Airflow (M³/h) | 2700 | 4100 | 5000 | 7500 | 12000 | 12000 | 17500 | 22000 | 28000 | 32000 | |
External ESP (Pa) | Nominal | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
Max External ESP (Pa) | 85 | 315 | 670 | 605 | 115 | 115 | 535 | 280 | 270 | 270 | |
Sound Pressure Level (dB(A))*4 | From Fan Discharge Downflow / Upflow | 64 / 63.9 | 71.4 / 71.3 | 68 / 68 | 74.8 / 74.8 | 81.5 / 81.5 | 81.5 / 81.5 | 77.2 / 77.2 | 82.5 / 82.5 | 83.4 | 83.4 |
From Unit Front Downflow / Upflow | 46 / 53 | 47.6 / 46.8 | 44.5 / 48.2 | 51.1 / 52.2 | 59.4 / 63.5 | 59.4 / 63.5 | 55.2 / 59.4 | 60.4 / 64.6 | 61.5 | 61.5 | |
Air Filters | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | |
Dimensions (mm) | Width x Depth x Height | 650 x 675 x 1925 | 785 x 675 x 1925 | 1085 x 775 x1925 | 1305 x 930 x 1980 | 1630 x 930 x 1980 | 1630 x 930 x 1980 | 2175 x 930 x 1980 | 2499 x 930 x 1980 | 2899 x 930 x 1980 | 2899 x 930 x 1980 |
Nett Weight (kg) | Downflow / Upflow | 220 / 210 | 250 / 240 | 330 / 320 | 440 / 430 | 490 / 480 | 575 / 565 | 705 / 650 | 865 / 805 | 985 | 1010 |
Power Supplt (V/Ph/Hz) | Three Phase 400/3/50+N | ||||||||||
Running Current (A) | MAX | 15.3 | 19.7 | 22.2 | 29.2 | 36.4 | 40.4 | 58.9 | 72.9 | 168 | 196 |
Starting Current (A) | 3.3 | 5.3 | 7.8 | 9.2 | 10.8 | 8 | 13.9 | 15.3 | 194 | 216 | |
Compressors | Type/No. | BLDC Rotary Inverter | 2x BLDC Scroll Inverter | 4x BLDC Scroll *5 | |||||||
Pipe Size Diameter (mm (in))*6 | Liquid | 12 (1/2") | 16 (5/8") | 16 (5/8") | 18 (3/4") | 18 (3/4") | 16 (5/8")*7 | 18 (3/4")*7 | 18 (3/4")*7 | 22 (7/8")*7 | 22 (7/8")*7 |
Gas | 16 (5/8") | 18 (3/4") | 18 (3/4") | 22 (7/8") | 28 (1 1/8") | 18 (3/4")*7 | 22 (7/8")*7 | 28 (1 1/8")*7 | 28 (1 1/8")*7 | 35 (1 3/8")*7 | |
Refrigerant | R410A | ||||||||||
Remote Condenser | Standard | M 14 | M 25 | M 30 | M 35 | M 60 | M 30 (x2) | M 35 (x2) | M 60 (x2) | M 95 (x2) | M 95 (x2) |
Outdoor Unit Model (T-MATE DX-A STD...) | M 14 | M 25 | M 30 | M 35 | M 60 | M 30 | M 35 | M 60 | M 95 | M 95 | |
Dimensions (mm) | W x D x H | 875 x 540 x 727 | 1400 x 665 x 1027 | 1850 x 665 x 1027 | 1400 x 665 x 1027 | 1850 x 665 x 1027 | 3490 x 665 x 1150 | ||||
Nett Weight | (kg) | 55 | 102 | 111 | 120 | 188 | 111 | 120 | 188 | 240 | 240 |
Airflow | (M³/h) | 4500 | 9600 | 9500 | 9100 | 16000 | 9500 | 9100 | 16000 | 28200 | 28200 |
Power Supply | (V/Ph/Hz) | Single Phase230 / 1 / 50 | |||||||||
Power Input (kW) | Nominal | 0.25 | 0.53 | 0.53 | 0.53 | 1.08 | 0.53 | 0.53 | 1.08 | 1.59 | 1.59 |
Max Run Current (A)) | 1.2 | 2.85 | 2.85 | 2.85 | 5.7 | 2.85 | 2.85 | 5.7 | 8.5 | 8.5 | |
Sound Pressure Level (dB(A)) | 1m (ISO3744) | 63 | 67 | 67 | 67 | 69.4 | 67 | 67 | 69.4 | 70.5 | 70.5 |
5m | 51.3 | 56.1 | 56.1 | 56.1 | 58.7 | 56.1 | 56.1 | 58.7 | 60.6 | 60.6 | |
10m | 45.6 | 50.5 | 50.5 | 50.5 | 53.2 | 50.5 | 50.5 | 53.2 | 55.3 | 55.3 |