VRF heat pump flexibility, efficiency and comfort delivered in a discrete, small capacity system.
New for 2018, The PUMY “SP” City Multi model allows up to 12 indoor units to be connected to a single outdoor unit, using the standard branch pipework system proven in the larger models. The new SP features a SINGLE FAN Condensing Unit allowing for simpler and more discreet installation in residential applications. Utilising the latest Mitsubishi Electric inverter technology, the system is fully controllable with all City Multi controllers or linked to third party BEMS.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Fuse Rating (Amps) | Pipe Size Gas | Pipe Size Liquid | Max Pipe (m) | Electrical Supply |
|
Combination | Outdoor Unit | |||||||
Max 9 FC, 130% | PUMY-SP112VKM | 12.50 | 14.00 | 32 A | 5/8 | 3/8 | 70 | Single |
Max 9 FC, 130% | PUMY-SP125VKM | 14.00 | 16.00 | 32 A | 5/8 | 3/8 | 70 | Single |
Max 10 FC, 130% | PUMY-SP140VKM | 15.50 | 16.50 | 32 A | 5/8 | 3/8 | 70 | Single |
This product is the Single Fan solution. 10kW – 20kW. Please click here for the Twin Fan optional model
Features and Benefits
Advanced Technical Data
Single Phase Condensing Units
Outdoor Unit Technical Data | Model Reference | ||
Model | PUMY-SP112YKM | PUMY-SP125YKM | PUMY-SP140YKM |
No. of Connectable Indoor Units | 9 | 10 | 12 |
Height (mm) | 1050 | ||
Width (mm) | 1050 | ||
Depth (mm) | 370 | ||
Weight (kG) | 93 | ||
Airflow (m3/min) | 77 | 81 | |
Sound Pressure Cooling (dBA) | 52 | 53 | 54 |
Liquid (mm(inches)) | 9.52 (3/8) | ||
Gas (mm(inches)) | 15.88 (5/8) | ||
Total Piping Length (m) | 120 | ||
Furthest Piping Length (m) | 70 | ||
Furthest Piping Length after 1st Branch (m) | 50 | ||
Between I/Unit and O/Unit - Height (m) | 50 (30 if O/Unit installed below) | ||
Between I/Unit and I/Unit - Height (m) | 15 | ||
Pre-charged to (m) | Please contact Logicool | ||
Standing Charge (kG) | 3.5 | ||
Additional grames per metre | Please contact Logicool | ||
Refrigerant | R410a | ||
Phase | Three | ||
Power Supply to | Outdoor | ||
Starting Current (A) | 7 | ||
System Running Current (A) Heating/Cooling | 4.82 / 4.71 | 5.93 / 5.83 | 6.11 / 7.14 |
Max Current (A) | 13 | ||
Fuse Rating (A) | 16 | ||
Interconnecting | 2 Core 1.5mm² Screened M-Net |
Three Phase Condensing Units
NOTE: AS OF FEB 18 THERE IS NO CONFIRMED AVAILABILITY OF THREE PHASE PRODUCT
Outdoor Unit Technical Data | Model Reference | ||
Model | PUMY-SP112VKM | PUMY-SP125VKM | PUMY-SP140VKM |
No. of Connectable Indoor Units | 9 | 10 | 12 |
Height (mm) | 1050 | ||
Width (mm) | 1050 | ||
Depth (mm) | 370 | ||
Weight (kG) | 93 | ||
Airflow (m3/min) | 77 | 81 | |
Sound Pressure Cooling (dBA) | 52 | 53 | 54 |
Liquid (mm(inches)) | 9.52 (3/8) | ||
Gas (mm(inches)) | 15.88 (5/8) | ||
Total Piping Length (m) | 120 | ||
Furthest Piping Length (m) | 70 | ||
Furthest Piping Length after 1st Branch (m) | 50 | ||
Between I/Unit and O/Unit - Height (m) | 50 (30 if O/Unit installed below) | ||
Between I/Unit and I/Unit - Height (m) | 15 | ||
Pre-charged to (m) | Please contact Logicool | ||
Standing Charge (kG) | 3.5 | ||
Additional grames per metre | Please contact Logicool | ||
Refrigerant | R410a | ||
Phase | Single | ||
Power Supply to | Outdoor | ||
Starting Current (A) | 14 | ||
System Running Current (A) Heating/Cooling | 13.48 / 13.18 | 16.58 / 16.33 | 17.09 / 19.98 |
Max Current (A) | 30.5 | ||
Fuse Rating (A) | 32 | ||
Interconnecting | 2 Core 1.5mm² Screened M-Net |