The Mr Slim R32 Power Inverter range blends a host of outstanding features with a premium quality, sophisticated design. Offering our highest
seasonal efficiency levels, advanced control options and extended pipe runs, this range is extremely flexible and available in four different
indoor unit types, from 3.5 to 14kW.
The R32 Power Inverter is able to achieve high seasonal efficiencies through the optimisation of a newly designed compressor and use of the latest energy-saving technologies.
ERP energy efficiency ratings of A++ are common throughout the range, with annual power consumption drastically reduced, resulting in increased run cost savings.
This page details specific information for Power Inverter Condensing Units only.
Twin – Quad combinations possible
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | Outdoor Fuse (Amps) | I/C Cable (Core) | Pipe Size Gas | Pipe Size Liquid | Electrical Supply |
|
Max. Indoors | Outdoor Unit | ||||||||
2 | PUZ-ZM71VHA | 7.10 | 8.00 | 55 | 25 | 3C + E | 5/8 | 3/8 | Single |
3 | PUZ-ZM100VKA | 10.00 | 11.20 | 100 | 32 | 3C + E | 5/8 | 3/8 | Single |
3 | PUZ-ZM125VKA | 12.50 | 14.00 | 100 | 32 | 3C + E | 5/8 | 3/8 | Single |
. | |||||||||
3 | PUZ-ZM140VKA | 14.00 | 16.00 | 100 | 40 | 3C + E | 5/8 | 3/8 | Single |
3 | PUZ-ZM100YKA | 10.00 | 11.20 | 100 | 10 | 3C + E | 5/8 | 3/8 | Three |
3 | PUZ-ZM125YKA | 12.50 | 14.00 | 100 | 16 | 3C + E | 5/8 | 3/8 | Three |
3 | PUZ-ZM140YKA | 14.00 | 16.00 | 100 | 16 | 3C + E | 5/8 | 3/8 | Three |
4 | PUZ-ZM200YKA | 19.00 | 22.40 | 120 | 32 | 3C + E | 1 1/8 | 3/8 | Three |
4 | PUZ-ZM250YKA | 22.00 | 27.00 | 120 | 32 | 3C + E | 1 1/8 | 1/2 | Three |
Features and Benefits
Compatible Units
Advanced Technical Data
Outdoor Unit Technical Data | Model Reference | ||||||
Connectivity | Single Split Only | Single / Twin | Single - Triple | Single - Quad | |||
Model | PUZ-ZM35VKA | PUZ-ZM50VKA | PUZ-ZM60VHA | PUZ-ZM71VHA | PUZ-ZM100V(Y)DA | PUZ-ZM125V(Y)DA | PUZ-ZM140V(Y)DA |
Height (mm) | 630 | 630 | 943 | 943 | 870 | 870 | 870 |
Width (mm) | 809 | 809 | 950 | 950 | 1100 | 1100 | 1100 |
Depth (mm) | 300 | 300 | 360 | 360 | 460 + 45 | 460 + 45 | 460 + 45 |
Weight (kG) | 46 | 46 | 70 | 70 | 107 | 107 | 107 |
Airflow (m3/min) | 45 | 45 | 55 | 55 | 80 | 84 | 97 |
Sound Pressure Cooling (dBA) | 44 | 44 | 47 | 47 | 44 | 47 | 49 |
Liquid (mm(inches)) | 6.35 (1/4) | 6.35 (1/4) | 9.52 (3/8) | 9.52 (3/8) | 9.52 (3/8) | 9.52 (3/8) | 9.52 (3/8) |
Gas (mm(inches)) | 12.7 (1/2) | 12.7 (1/2) | 15.88 (5/8) | 15.88 (5/8) | 15.88 (5/8) | 15.88 (5/8) | 15.88 (5/8) |
Max Pipe Run (m) | 50 | 50 | 55 | 55 | 100 | 100 | 100 |
Max Pipe Lift (m) | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
Pre-charged to (m) | 30 | 30 | 30 | 30 | 40 | 40 | 40 |
Standing Charge (kG) | 2.0 | 2.0 | 2.8 | 2.8 | 3.6 | 3.6 | 3.6 |
Additional Charge per m (g) | 15 | 15 | 40 | 40 | 40 | 40 | 40 |
Refrigerant | R32 | R32 | R32 | R32 | R32 | R32 | R32 |
Phase | Single | Single | Single | Single | Single (Three) | Single (Three) | Single (Three) |
Power Supply to | Outdoor | Outdoor | Outdoor | Outdoor | Outdoor | Outdoor | Outdoor |
Max Current (A) | 13.2 | 13.2 | 19.2 | 19.2 | 26.5 (8.0) | 26.50 (9.0) | 30.0 (9.0) |
Fuse Rating (A) | 16 | 16 | 25 | 25 | 32 (16) | 32 (16) | 40 (16) |
Interconnecting | 3C+E | 3C+E | 3C+E | 3C+E | 3C+E | 3C+E | 3C+E |
System Power Input (Cool/Heat) - kW | 0.71 / 0.82 | 1.11 / 1.36 | 1.45 / 1.71 | 1.65 / 1.82 | 2.16 / 2.67 | 3.47 / 3.89 | 3.66 / 4.57 |
Twin Pipe Kit | N/A - Single Split Only | N/A - Single Split Only | N/A - Single Split Only | MSDD-50TR2-E | |||
Triple Pipe Kit | N/A - Single Split Only | N/A - Single Split Only | N/A - Single Split Only | N/A Single - Twin Only | MSDT-111R3-E | ||
Quad Pipe Kit | N/A - Single Split Only | N/A - Single Split Only | N/A - Single Split Only | Single - Twin Only | Single - Triple Only | MSDF-1111R-E |
Outdoor Unit Technical Data | Model Reference | |
Model | PUZ-ZM200YKA | PUZ-ZM250YKA |
Height (mm) | 1338 | |
Width (mm) | 1050 | |
Depth (mm) | 330 + 40 | |
Weight (kG) | 137 | 138 |
Airflow (m3/min) | 140 | |
Sound Pressure Cooling (dBA) | 59 | 59 |
Sound Pressure Heating (dBA) | 62 | 62 |
Liquid (mm(inches)) | 9.52 (3/8) | 12.7 (1/2) |
Gas (mm(inches)) | 28.58 (1 1/8) | 28.58 (1 1/8) |
Max Pipe Run (m) | 100 | |
Max Pipe Lift (m) | 30 | |
Pre-charged to (m) | 30 | |
Standing Charge (kG) | 6.3 | 6.8 |
Additional Charge per m (g) | 40 | 60 |
Refrigerant | R32 | |
Phase | Three | |
Power Supply to | Outdoor | |
Max Start/Run Current (A) | 5.00 / 9.57 | 5.00 / 13.30 |
Max Current (A) | 22.50 | |
Fuse Rating (A) | 32 | |
Interconnecting | 3C+E | |
System Power Input (Cool/Heat UK) - kW | 5.18 / 4.89 | 6.43 / 6.13 |
Twin Pipe Kit | MSDD-50WR2-E | |
Triple Pipe Kit | MSDT-111R3-E | |
Quad Pipe Kit | MSDF-1111R2-E |