PACi Standard: For economy and value
With high quality design and engineering, the PACi Standard is the perfect solution for projects which demand quality on a limited budget. In addition, its compact size and light weight make it ideal for installations with limited space including small commercial and residential applications.
The outdoor unit is much more compact than the previous model. The slim and lightweight design means the PACi outdoor unit can be installed in a number of situations.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) In/Out | Pipe Size Gas | Pipe Size Liquid | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | |||||||
S-60PK2E5A | U-60PZ2E5 | 6.10 | 6.10 | 40 | 4.70 | 6.80 | 20 | 5/8 | 3/8 | Single |
S-71PK2E5A | U-71PZ2E5 | 7.10 | 7.10 | 40 | 4.60 | 6.40 | 20 | 5/8 | 3/8 | Single |
S-100PK2E5A | U-100PZ2E5 | 9.00 | 9.00 | 50 | 3.90 | 6.50 | 25 | 5/8 | 3/8 | Single |
S-100PK2E5A | U-100PZ2E8 | 9.00 | 9.00 | 50 | 3.90 | 6.50 | 16 | 5/8 | 3/8 | Three |
System Combination
Options
Features and Benefits
New PACi R32 Refrigerant Gas
Panasonic recommended R32 because it is environmental friendly.
Compared to R22 and R410A, R32 has a very low potential impact on the depletion of ozone layer and global warming.
In line with the European Countries who are concern in protecting and maintaining the environment by participating the Montreal Protocol to rectify one of its program in protecting the Ozone Layer and preventingGlobal Warming, Panasonic is leading the switch to R32.
1. Installation innovation.
· Extremely easy to install, practically the same as for the R410A (just remember to verify that the pressure gauge and vacuum pump are compatible with the R32)
· This refrigerant is 100% pure, which makes it easier to recycle and reuse
2. Environmental innovation.
· Zero impact on the ozone layer
· 75% less impact on global warming
3. Economic and energy consumption innovation.
· Lower cost and greater savings
· Higher energy efficiency than R410A
Product Images
Power/Wiring
Panasonic PAC-i systems require a separate power supply to Indoor (3 Amp isolator for all units) and Outdoor Units. It is also possible to supply power to outdoor unit only, and run power to indoor via a 3 core flex from a field supplied fused terminal block. A separate 2 core 0.75mm² screened cable will also be required for data connection
Advanced Technical Data
Indoor Unit Technical Data | |||||
Model | S-36PK1E5B | S-50PK1E5B | S-60PK1E5B | S-71PK1E5B | S-100PK1E5B |
Cooling (kW) - Nominal | 3.6 | 5.0 | 6.0 | 7.1 | 9.0 |
Heating (kW) - Nominal | 3.6 | 5.0 | 6.0 | 7.1 | 9.0 |
Cooling (kW) - Max SEER Condition | Multi | 7.1 | 7.7 | 9.7 | |
Heating (kW) - Max SCOP ACC | Multi | 7.0 | 8.1 | 10.5 | |
Sensible Heat Capacity (SHC) | Multi | 5.5 | 5.6 | 6.2 | |
Sound Pressure Level (dBA) | 35/31/37 | 40/36/32 | 47/44/40 | 47/44/40 | 49/45/41 |
Height - mm (grille) | 300 | ||||
Width - mm (grille) | 1120 | ||||
Depth - mm (grille) | 230 | ||||
Weight - kG (grille) | 14 | ||||
Air Flow Rate (m³/min) | 13.0/11.0/9.0 | 16.0/13.5/11.0 | 20.0/17.5/14.5 | 20.0/17.5/14.5 | 22.0/18.5/15.0 |
Fused Spur (A) | 5 |
Outdoor Unit Technical Data | |||||
Combinations | Single | Single and Twin | |||
Model | U-60PZ2E5 | U-71PZ2E5 | U-100PZ2E5(8) | U-125PZ2E5(8) | U-140PZ2E5(8) |
Height (mm) | 695 | 695 | 996 | 996 | 1416 |
Width (mm) | 875 | 875 | 980 | 940 | 940 |
Depth (mm) | 320 | 320 | 370 | 340 | 340 |
Weight (kG) | 44 | 44 | 90 | 94 | 94 |
Airflow (m3/min) | 40 / 45 | 50 / 45 | 76 / 70 | 86 / 78 | 89 / 83 |
Sound Pressure Cooling (dBA) | 48 | 49 | 52 | 55 | 56 |
Sound Power Cooling (dBA) | 68 | 69 | 70 | 73 | 74 |
Liquid (mm(inches)) | 9.52 (3/8) | ||||
Gas (mm(inches)) | 15.88 (5/8) | ||||
Max Pipe Run (m) | 40 | 50 | |||
Max Pipe Lift (m) | 30 (15 if condenser is lower than IU) | ||||
Pre-charged to (m) | 30 | ||||
Standing Charge (kG) | 1.45 | 1.45 | 2.6 | 2.98 | 2.98 |
Additional Charge/m (g) | 35 | 35 | 45 | 45 | 45 |
Refrigerant | R32 | ||||
Phase | Single | Single (Three) | |||
Power Supply to | IU (5A) and OU or OU with feed to IU | ||||
Max Current (A) | 16.4 | 16.34 | 25.0 | 29.0 | 30.0 |
Fuse Rating (A) | 20 | 20 | 25 (16) | 32 (16) | 32 (16) |
Interconnecting | 2C Screen 0.75mm² |
||||
Twin Pipe Kit | CZ-P224BK2BM |