SOLUTIONS FOR SERVER ROOMS
New Wall Mounted Professional with high efficiency even at -15 °C
Non-stop operation. 24/7. 365
High efficiency products for 24/7 applications.
Panasonic has developed a complete range of solutions for server rooms which effi ciently protect your servers, keeping them at an appropriate temperature even when the outdoor temperature is below -20°C.
Back-up and Rotate option for two systems
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) | Pipe Size Gas | Pipe Size Liquid | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | |||||||
CS-Z25TKEA | CU-Z25TKEA | 2.50 | 3.40 | 20 | 4.50 | 8.50 | 16 | 3/8 | 1/4 | Single |
CS-Z35TKEA | CU-Z35TKEA | 3.50 | 4.00 | 20 | 4.40 | 8.50 | 16 | 3/8 | 1/4 | Single |
CS-Z42TKEA | CU-Z42TKEA | 4.20 | 5.40 | 20 | 4.30 | 8.50 | 16 | 1/2 | 1/4 | Single |
CS-Z50TKEA | CU-Z50TKEA | 5.00 | 5.80 | 30 | 4.40 | 8.50 | 16 | 1/2 | 1/4 | Single |
CS-Z71TKEA | CU-Z71TKEA | 7.10 | 8.60 | 30 | 4.00 | 6.10 | 20 | 5/8 | 1/4 | Single |
Comes complete with Hard Wired controller in packaging
Product Description
High efficiency all the year: On 24/7 operation, the performance of the air conditioning is a key factor. When the efficiency is high, the return on investment of such units is quickly reached.
Complete line-up with high efficiency even at -20°C: This Wall Mounted air conditioner is especially designed for professional applications such as computer rooms where cooling inside the room is necessary even when the outside temperature is low. Furthermore this air conditioner has an automatic changeover system, in order to maintain the inside temperature even when sharp outside temperature changes occur.
Outdoor Unit · Cooling even when ambient temperature is as low as -20°C · Electronic expansion valve (accurate sub-cooling and adjustable refrigerant flow) · Outdoor DC fan motor to provide flexible air-fl ow to ensure optimum condensation pressure (works on outdoor pipe temperature sensor)
Interface option to manage server room operation: The PAW-SERVER-tKEA server room interface manages redundancy and backup of two PKEA units with two different selectable modes: · Plug and play by embedded redundancy and backup algorithm (no external signal needed. Further details please refer to operation manual) · External (third party PLC) redundancy and backup management by dry contact All settings are possible without the need for a computer connection. A special Energy Saving Mode is selectable by deep switch (available only in plug and play mode). The level of remote control input prohibition can be set when external management is by dry contact.
Features and Benefits
Product Images
Advanced Product Data Tables
Indoor Unit Technical Data | Model Number | ||||
CS-E25TKEA | CS-E35TKEA | CS-E42TKEA | CS-E50TKEA | CS-E71TKEA | |
Cooling (kW) - Nominal | 2.50 (0.85 - 3.00) | 3.50 (0.85 - 4.00) | 4.20 (0.98 - 5.00) | 5.00 (0.98 - 6.00) | 7.10 (0.98 - 8.10) |
Heating (kW) - Nominal | 3.40 (0.85 - 5.40) | 4.00 (0.85 - 6.60) | 5.40 (0.98 - 7.25) | 5.80 (0.98 - 8.00) | 8.60 (0.98 - 9.90) |
Cooling (kW) - Max UK Condition | 3.00 | 4.00 | 5.00 | 6.00 | 8.10 |
Heating (kW) - Max UK Condition | 5.40 | 6.60 | 7.25 | 8.00 | 9.90 |
Sensible Cooling Duty (UK) | 1.90 | 2.66 | 3.19 | 4.25 | 5.20 |
Sound Pressure - Cooling (dBA) | 39 / 25 / 21 | 42 / 28 / 21 | 43 / 32 / 29 | 44 / 37 / 30 | 47 / 38 / 35 |
Sound Pressure - Heating (dBA) | 41 / 27 / 22 | 43 / 30 / 22 | 44 / 35 / 29 | 44 / 37 / 30 | 47 / 38 / 35 |
Height (mm) | 295 | 302 | |||
Width (mm) | 919 | 1120 | |||
Depth (mm) | 194 | 236 | |||
Weight (kG) | 9 | 10 | 12 | 12 | 13 |
Air Flow - Cooling (m³/min) | 10.4 | 10.7 | 18.2 | 19.2 | 20.2 |
Air Flow - Heating (m³/min) | 11.7 | 12.4 | 20.2 | 21.3 | 21 |
Outdoor Unit Technical Data | Model Number | ||||
CU-E25TKEA | CU-E35TKEA | CU-E42TKEA | CU-E50TKEA | CU-E71TKEA | |
Height (mm) | 619 | 619 | 619 | 695 | 695 |
Width (mm) | 824 | 824 | 824 | 875 | 875 |
Depth (mm) | 299 | 299 | 299 | 320 | 320 |
Weight (kG) | 37 | 38 | 38 | 43 | 49 |
Sound Pressure - Cooling (dBA) | 46 | 48 | 48 | 48 | 52 |
Sound Pressure - Heating (dBA) | 48 | 50 | 50 | 50 | 54 |
Liquid (mm(inches)) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) |
Gas (mm(inches)) | 9.52 (3/8) | 9.52 (3/8) | 12.7 (1/2) | 12.7 (1/2) | 15.88 (5/8) |
Max Pipe Run | 20 | 20 | 20 | 30 | 30 |
Max Pipe Lift | 15 | ||||
Pre-charged to (m) | 7.5 | 10 | |||
Standing Charge (kG) | 0.96 | 1.00 | 1.08 | 1.15 | 1.32 |
Additional g/m | 10 | 10 | 10 | 15 | 25 |
Refrigerant | R32 | ||||
Phase | Single | ||||
Power Supply to | Indoor | ||||
Start Current (A) | |||||
Fuse Rating (A) | 16 | 16 | 16 | 16 | 20 |
Interconnecting | 3C + E | ||||
System Power Input (Cool/Heat) - kW | 0.51 / 0.70 | 0.86 / 0.92 | 1.10 / 1.35 | 1.39 / 1.44 | 2.24 / 2.45 |